Page 197 - Handbook of Electrical Engineering
P. 197

180    HANDBOOK OF ELECTRICAL ENGINEERING

































              Figure 8.3  Peak cut-off current versus prospective symmetrical rms current for typical fuses in the range of
              100 A to 200 A.


                    See Table H.1b for X-to-R ratio of 25, the doubling factor is 2.661.
                    Therefore the peak asymmetrical current is I pkasym ,

                                     I pkasym = 13,122 × 2.661 = 34,944 amps pk

              Step 4.  Decide upon suitable cut-off current.
                    Choose the maximum cut-off current to be 45% of the peak asymmetrical fault current

                                      I pkcutoff = 0.45 × 34,944 = 15,724 amps pk
                                      Round this up to 16,000 amps pk

              Step 5.  Select the largest fuse to suit the cut-off limit.
                    Use Figure 8.3 even through the prospective current is shown as rms symmetrical. This
              example is a special case since the X-to-R ratio is known.
                                                      34,944
                                   Prospective current =  √  = 24,713 amps rms
                                                         2
              Hence the ‘largest’ fuse for cut-off limit is 160 amp rating.
              Step 6.  Compare the I-squared-t characteristic of the fuses with the I-squared-t characteristic of
              the cables, in Figure 8.4. A 160 amp fuse will protect the 35 mm sq cable for fault currents beyond
   192   193   194   195   196   197   198   199   200   201   202