Page 239 - Handbook of Electrical Engineering
P. 239

CABLES, WIRES AND CABLE INSTALLATION PRACTICES     223

                               Table 9.25. Cable-sizing chart for DOL induction motors

                                                            Cable information
                                                          EPR cable size in mm 2
                     Motor            2.5  4   5  10  16  25  35  50  70  95  120  150  185  240
                   information
           Motor  Motor  Motor  Motor
           rating  FLC   FLC   I s /I n                 Derated cable current in amps
            (kW)  current  power  ratio
                  (A)    factor
            11      19    0.86   6.5  19  26  33  46  62  83  99 124 159 193  223  253  288  343
            15      25    0.87   7.2  Maximum route length in metres (in this case limited by starting current)
            18.5    30    0.89   7.0      105 156 254 389
            22      36    0.88   7.0          99 162 249 375
            30      51    0.86   7.0             123 190 287 377
            37      63    0.85   7.0             106 164 249 328
            45      76    0.85   7.0                 110 166 219 278
            55      94    0.84   7.0                     187 241 299 379
            75     124    0.86   7.0                     155 200 248 314
            90     146    0.87   7.0  Note:                  164 204 257 307
           110     178    0.88   7.0  a) Volt-drop on starting 15%.  154 195 233  276
           132     214    0.88   7.0  b) Volt-drop at full-load 5%.  165 198  234  256
                                                         ◦
           150     243    0.88   7.0  c) Ambient temperature 30 C.       162  192  210  230
           185     297    0.88   7.0  d) System voltage 440 V at 60 Hz.       163  178  194  210
           200     317    0.89   7.0  e) Cable derating factor for ambient         156  171  185
                                        temperature and grouping in air is 0.93.       152  158
                                                                                            148


           Let

                                                      θ 2 + 234.5
                                           2
                                                2
                                          K = k log
                                                    e
                                                      θ 1 + 234.5
           For copper conductors
                                             k = 226
                                                          160 + 234.5

                                      2
                                                    2
                                    K for PVC = 226 log e
                                                           70 + 234.5
                                                    2
                                               = 226 × 0.25589
           Therefore
                                             K = 226 × 0.5088 = 115

           Similarly for XLPE and EPR, K = 143.
                                                               ◦
                                                                                             ◦
                 For bare copper in air with a final temperature of 150 C and an initial temperature of 70 C
                                                                                ◦
           the value of K is 109. If the initial current is zero and the initial temperature is 30 Cthen K is 138.
                                                                                         ◦
           See Table 54 B of IEC60364 Part 5, Chapter 54. If the final temperature is allowed to be 250 Cthen
           the value of K will be in the order of 170 to 180.
                 In the calculation of short-circuit current it is usually assumed that this current is much larger
           than the normal load current even if it is its full-load value. Hence I fl in (9.6) can be ignored, thereby