                                    Figure 9.5 Cut-off and prospective current of fuses.


                    For the selection of fuses the prospective symmetrical rms value of the off-set fault current
              I frms is calculated as,

                                                          147,654
                                                   I fpka
                                            I frms = √ =    √
                                                   2 2     2 2
                                                       = 52,204 amps

                    From the graphical characteristics given by the manufacturer the maximum fuse rating can be
              selected, see Figure 9.5.
                    The maximum fuse rating is 315 A and so the choice of 200 A is satisfactory.
                    Select a cable and check that its I-squared-t characteristics are adequate.
                    From Table 9.17 the derating for ambient temperature K air is 0.92 and assume no derating for
                                                                                            2
                                                                              ◦
              the grouping of cables. Hence the nearest cable rating to carry 200 amps at 35 Chas a 70 mm cross-
              sectional area. This cable has a thermal energy constant K of 143. Hence its time-current characteristic
              is given by two or more points on a straight line on a log-log graph. From the following,
                                         √     KA    143 × 70   10010.0
                                           t =     =          =
                                                I       I          I

              Several suitable points on the graph are given in Table 9.27.