Page 256 - Handbook of Electrical Engineering
P. 256

240    HANDBOOK OF ELECTRICAL ENGINEERING

                           Table 9.34. Earth loop impedance results for the worked example with
                           braided armouring
                           Nominal conductor       Z a + Z c         Z loopc     V shock
                                     2
                              area (mm )                            magnitude
                                                                     (ohms)
                                 16           4.916 + j0.0268        5.9193     227.49
                                 25           5.807 + j0.0250        6.8102     232.91
                                 35           2.221 + j0.0242        3.2244     229.31
                                 50           2.462 + j0.0236        3.4654     232.45
                                 70           2.791 + j0.0224        3.7944     235.03



                                         Z mr = 1.0 + j0.0 ohms
                                         Z c and Z a are given in c)


                 The resulting Z loopc calculated from the circuit for each cable is given in Table 9.34.
                 Comparing the tabulated results above with those for the fuses in d) shows that all the cables
                 have an earth loop impedance much greater than that permitted by the fuse, by a ratio of approx-
                 imately 10:1.

                 Hence an earth leakage circuit breaker should be used in the MCC to protect the circuit against
                 electric shock hazard.
                 The most appropriate choice of cable cross-sectional area and fuse rating are,

                                                               2
                 • Cable cross-sectional area should be at least 50 mm , to comply with volt-drop.
                 • Fuse rating should be below the rating of the cable since its primary purpose is to protect the
                                                                     2
                   cable. Hence the largest fuse should be 125 A for a 50 mm cable. (If a larger fuse is needed
                   the cable size would need to be increased.)
              h) Calculate the electric shock voltage
                 From Figure 9.9 the shock voltage V shock is,


                                                       (Z a + Z mr )V ph
                                            V shock =
                                                    Z sec + Z c + Z a + Z mr
                              2
                 For the 16 mm cable

                                               4.62 + 1.0    415
                                       V shock =          √    = 227.49 volts
                                                5.9193      3

               i) Replace the braided armour with round steel wires.
                 Assume the resistances of the armour wires to be 0.72, 0.50, 0.46, 0.40 and 0.36 ohms for the
                 200 m route length. Repeat the calculations of g).
   251   252   253   254   255   256   257   258   259   260   261