Page 254 - Handbook of Electrical Engineering
P. 254

238    HANDBOOK OF ELECTRICAL ENGINEERING

                                      Table 9.30. Cable data for the worked example

                       Nominal      Current         3-core conductor        GSWB armouring
                       conductor    rating
                             2
                                       ◦
                      area (mm )    at 40 C   Resistance at  Reactance at      resistance
                                                 ◦
                                    (amps)     90 C ohms     50 Hz (ohms)       (ohms)
                                                  R c            X c              R a
                          16        0.2960       0.0268         4.62             70.35
                          25        0.1872       0.0250         5.62             93.45
                          35        0.1348       0.0242         2.086            110.3
                          50        0.0998       0.0236         2.362            141.8
                          70        0.0688       0.0224         2.722            178.5


                                      Table 9.31. Fuse data for the worked example

                              Fuse rating   Operating current   Maximum earth loop
                              (amps)           at 5.0 sec     impedance at 240 V/phase
                                                (amps)             Z loopf (ohms)

                                 100             500                 0.4792
                                 125             650                 0.3686
                                 160             850                 0.2819
                                 200            1100                 0.2179


                                      Table 9.32. Cable data for the worked example
                     Fuse rating   Operating current  Minimum conductor    Nearest practical
                                                                2
                                                                                         2
                       (amps)      at 5.0 sec (amps)  CSA A min (mm )    CSA above A min (mm )
                        100             500                7.82                  10
                        125             650               10.17                  16
                        160             850               13.29                  16
                        200            1100               17.20                  25



                 Where K = 143 for EPR insulation and A min is the smallest conductor cross-sectional area.
                 The resulting A min for the four sizes of fuses are given in Table 9.32:
                                        2
                                                 2
                 Hence all the cables 16 mm to 70 mm in c) that suit the motor full-load current will be adequately
                 protected by the fuses in the range given.
               f) Calculate the volt-drops for running and starting the motor.
                 From (9.3) for ‘running’ conditions,

                                           cos Ø = 0.85 and sin Ø = 0.5268

                                                     2
                 Assume the cable conductor area is 16 mm ,
                 Therefore,

                                     R = 0.2960 ohms and X = 0.0268 ohms
   249   250   251   252   253   254   255   256   257   258   259