Page 250 - Handbook of Electrical Engineering
P. 250

234    HANDBOOK OF ELECTRICAL ENGINEERING
































                                       Figure 9.8 Earth loop impedance diagram.

              For TT and IT systems:

                                     Z loop = Z nez + Z sec + Z c + Z a + Z bond + Z er      (9.10)

              These components are shown in Figure 9.8.

              Where Z nez is the impedance of the neutral earthing device at the source winding.
                     Z sec is the positive sequence impedance of the source. For a transformer this includes
                          both windings and the upstream impedance. For a generator this will be the
                          sub-transient impedance.
                       Z c is the impedance of one phase conductor of the particular cable.
                      Z a is the impedance of its armouring of the particular cable. This impedance can be
                          taken as purely resistance (R a ).
                    Z bond is the impedance of the earthing terminals and bonding conductors at the sending
                          end of the cable.
                      Z mr is the metallic return path impedance of a TN system. This impedance can be
                          taken as purely resistance, but will usually be low enough to ignore. For offshore
                          installations the multiple series and parallel branches of steel work in three
                          dimensions will render such an impedance as almost zero.
                      Z er is the impedance of the earth return path of the ground for a TT or IT system. It
                          will be approximately the total impedance of the ground rod or grid at the source
                          and the ground rod or grid at the consumer. The impedance will be almost purely
                          resistance, being typically a fraction of an ohm for damp soil conditions to several
                          ohms for dry sandy and rocky soils. See also the international standard IEEE 80,
                          1986, section 12.
   245   246   247   248   249   250   251   252   253   254   255