CABLES, WIRES AND CABLE INSTALLATION PRACTICES     241

                         2
              For a 16 mm cable,
                                    Z a + Z c = 0.2960 + j0.0268 + 0.72 = 1.016 + j0.0268

                                      Z loopc = Z a + Z c + Z sec + 0.1
                                           = 1.016 + j0.0268 + 0.00308 + j0.0308 + 0.1
                                           = 1.119 + j0.0576

                          Magnitude of Z loopc = 1.1206 ohms
              The resulting Z loopc calculated from the circuit for each cable is given below,
                           2
              For the 16 mm the shock voltage is,
                                            0.72 + 0.1    415
                                     V shock =          √    = 175.3 volts
                                              1.1206     3

                       2
              If a 50 mm cable and a fuse rating of 125 amps are chosen as recommended in g) then the circuit
              earth loop impedance is still too high by a ratio of about 1.65:1. Hence an earth leakage circuit
              breaker should still be used for this motor circuit. The hazardous shock voltage is still too high.
            j) Now replace the fuses with moulded case circuit breakers and show whether or not the situation
              is improved. From Figure 7.9 it can be seen that a typical MCCB for motor application operates
              in its inverse region for times equal to 5.0 seconds.
              Repeating d) but for MCCBs gives the following limits for Z loopf ,


                        Table 9.35. Earth loop impedance results for the worked example with steel
                        wire armouring
                        Nominal conductor        Z a + Z c         Z loopc    V shock
                               2
                        area (mm )                               magnitude
                                                                  (ohms)
                               16          1.016 + j0.0268        1.1206      175.3
                               25          0.6872 + j0.0250       0.7922      181.5
                               35          0.5948 + j0.0242       0.6999      191.7
                               50          0.4998 + j0.0236       0.6053      197.9
                               70          0.4288 + j0.0224       0.5344      206.2


                           Table 9.36. Limiting values of earth loop impedance when MCCB
                           is used
                           MCCB rating    Lowest operating    Maximum earth loop
                           (amps)           current at     impedance at 240 V/phase
                                           5.0 sec (amps)       Z loopf (ohms)
                              100              370                 0.6476
                              125              470                 0.5098
                              160              720                 0.3328
                              200              900                 0.2662