314    HANDBOOK OF ELECTRICAL ENGINEERING

              • Reverse active power (32).
              • Negative phase sequence (46).
              • Stator earth fault current (51 G) and (64).
              • Over terminal voltage, (59) Note 1.
              • Under terminal voltage, (27) Note 1.
              • Overfrequency, (81) Note 2.
              • Underfrequency, (81) Note 2.
              • Winding temperature (26).
              Note 1: These can be combined in one voltage relay.
              Note 2: These can be combined in one frequency relay.


              A typical scheme that contains most of these relays is shown in Figure 12.2.


              12.2.2 Overcurrent
              12.2.2.1 Response of a generator to a major fault

              When a major fault occurs externally from the generator but near to the generator stator terminals or
              near its switchgear, two reactions take place:-





































                                 Figure 12.2 Protective devices for a high voltage generator.