Page 332 - Handbook of Electrical Engineering
P. 332

PROTECTIVE RELAY COORDINATION      319

































           Figure 12.7 Effect of a large load variation on the response of overcurrent relays at the generators. The
           diagram shows the response when a large induction motor is started direct-on-line. Four different standing loads
           are shown.


           for longer than several seconds, see Reference 2. The relay itself should function in approximately
           15 milliseconds, and have a sensitivity of about 2 to 5% of the stator rated current. The nominal
           setting ranges are between 10 to 40% for 1amp relays and 20 to 80% for 5 amp relays. The low %
           settings are usually chosen initially and increased if subsequently found to be too sensitive. This type
           of protection is generally applied to high voltage machines above about 2 MW.
                 Electromagnetic differential current relays are fitted with restraining or biasing, coils in each
           secondary circuit of their current transformer. These restraining coils stabilise the relay when large
           ‘through’ fault currents are present in the windings i.e. feeding an external fault. Stabilisation is
           necessary because of mismatch errors and saturation effects in the current transformers, which would
           otherwise be large enough to activate the sensitive operating coil.


           12.2.4 Field Failure Relay


           If the field is lost in a generator it will attempt to generate power at a low leading power factor and
           with a large rotor angle. In most loading situations the generator rotor angle will increase to a critical
           value where unstable power transfer will occur, and the generator will no longer be able to remain in
           synchronism with the supply. When synchronism is lost the stator current varies in magnitude over
           a wide range and at the slip frequency. If this is allowed to continue then it is possible that damage
           will result in the stator and rotor windings, and the disturbance in voltage at the connected power
           network will be large enough to cause tripping and overcurrents in loads.
   327   328   329   330   331   332   333   334   335   336   337