Page 337 - Handbook of Electrical Engineering
P. 337

324    HANDBOOK OF ELECTRICAL ENGINEERING

              the current transformer to balance the ampere-turns across its windings. It is the normal practice to
              shunt the relay with a non-linear resistor. As the voltage across the resistor and the relay rises above
              a predetermined value, the resistor shunts more and more current from the current transformer. In so
              doing the relay voltage is moderated, and the relay functions as required.
                    The choice of current or voltage setting for the relay will depend upon the design value of
              earth fault current that will pass in the NER during the specified time e.g. 20 amps for 10 seconds. If
              the setting is too low the relay may respond to stray and harmonic currents in the neutral circuit. The
              maximum expected third plus triplen currents should be determined and the relay set at say double
              their combined level, or higher.
                    It is worth noting that the stator differential relays (87) will not normally be sensitive enough
              to detect the low earth fault currents that are limited by a high resistance NER. With the modern
              practice being to limit these currents to typically 20 amps, it is necessary to install the restricted earth
              fault relays (64).


              12.2.8 Over Terminal Voltage

              If the terminal voltage of a generator persists above about 110% of its nominal value then it is
              possible that the automatic voltage regulator (AVR) of the generator has developed a fault within its
              control circuits. (An alternative cause, in the case of generators having a high neutral earth resistance,
              is that an earth fault on one phase is present.)
                    Excessive terminal voltage from the generator implies that the exciter is being forced to
              produce a high rotor current in the generator. Consequently both the generator itself and its exciter
              are being overstressed in terms of current, and therefore may become overheated.
                    Since the generator is supplying the power system at an elevated voltage, all the transformers
              and consumers near to the generator will receive an excessive voltage. In this situation transformers
              and motors in particular may well be overexcited and their magnetising current will rise sharply.
              Excessive magnetising current may be accompanied by overheating of the iron core laminations.
              Other consumers such as inverters, battery chargers, light fittings, electronic systems may also react
              unfavourably to excessive supply voltage.

                    If several generators are operating in parallel and one of them has a faulty AVR then the
              healthy generators may become underexcited as their AVRs respond to the high system voltage. This
              situation could lead to unstable operation if the generator rotor angles become too large.

                    To protect the system from prolonged high voltage it is the usual practice to install an over-
              voltage relay (59) in each of the generator circuit breakers or at their common busbar. The relay
              settings are usually set to operate at 115%, with a time delay between 0.5 and 10.0 seconds.


              12.2.9 Under Terminal Voltage

              Prolonged undervoltage implies that there is a fault in the AVR or that there is an excess current being
              drawn from the generator. An excessive current could be due to a fault in the system or an overload
              caused by, for example, a loss of a generator without a corresponding shedding of load. If the cause is
              excessive current but the voltage is still high enough to maintain the consumers, then the overcurrent
              protection of the generator may take too long to operate, particularly if a voltage-restrained relay
   332   333   334   335   336   337   338   339   340   341   342