Page 334 - Handbook of Electrical Engineering
P. 334

PROTECTIVE RELAY COORDINATION      321

                 Conversion factor for referring the generator reactances to the CT and VT secondary circuits:-

                                                       2
                                            X gen % × V gen × CT ratio
                                      X sec =
                                              100 × S gen × VT ratio
                                                        2
                                            X gen % × 6600 × 800 × 110
                                          =
                                             100 × 750,0000 × 1 6600
                                            X gen %
                                          =       × 5.808 × 13.333
                                             100
                                      X sec = X gen % × 0.7744 ohms
                                     X    = 25.0 × 0.7744 = 19.36 ohms
                                       dsec
                                     X dsec = 250.0 × 0.7744 = 193.6 ohms
                 Choose an offset of 0.75 X , a circle diameter of 0.5X d . This will allow the generator to run

                                        d
           in the leading power factor zone with a large transient rotor angle (up to 120 degrees).
                                Relay offset = 0.75 × 19.36 = 14.52 ohms
                                              rounded to 15.0 ohms
                                Relay circle diameter = 0.5 × 193.6 = 96.8 ohms

                                                     rounded to 100.0 ohms
                                Relay time delay, choose 4 seconds.

           These results are shown in Figure 12.8.

           12.2.5 Reverse Active Power Relay
           Reverse active power protection (32) is required to prevent the prime mover from being driven by
           the generator. This can occur during transient disturbances when a generator is lightly loaded, the






















           Figure 12.8 Loss of excitation characteristic of an admittance relay. The diagram is drawn in the impedance
           domain.
   329   330   331   332   333   334   335   336   337   338   339