Page 354 - Handbook of Electrical Engineering
P. 354

PROTECTIVE RELAY COORDINATION      341


































           Figure 12.18 Motor run-up, thermal and instantaneous relay curves. The cold and hot thermal images of
           the relay are presented. The stalling conditions are indicated. The increase in the motor run-up time due to a
           reduction in terminal voltage is shown.


                 Should the stalling time be less than the corresponding cold thermal image time for the same
           stalling current then the relay will not detect the condition. Either the relay thermal settings will need
           to be reduced, if possible, or a separate special timing relay used instead.


           12.7.7 Limitation to the Number of Successive Starts

           Repeated starting of a motor in close succession will cause the accumulation of heat in the conductors
           and body of the motor. To safeguard against damage it is desirable to limit the number of starting
           attempts that are made in a predetermined time period. A well-specified motor will have a prescribed
           number of starting attempts, e.g. 2 to 5, and a rest period before the same attempts are repeated. The
           rest period is typically 0.5 to 1.0 hour. This should apply especially to motors that have long starting
           periods, such as motors that drive high-speed compressors.
                 Modern microcomputer based relays are easily able to provide this function.


           12.7.8 Undercurrent


           Most high voltage motors used in the oil industry operate at steady loads between 75% and 90% of
           their rated power capability. Should the motor suddenly find itself underloaded then it is possible that
           the driven machine has inadvertently lost its load, e.g. a pump loses liquid at its suction port. This
   349   350   351   352   353   354   355   356   357   358   359