Page 357 - Handbook of Electrical Engineering
P. 357

344    HANDBOOK OF ELECTRICAL ENGINEERING


































                               Figure 12.20 Thermal and instantaneous curves of a motor relay.

                    Hot and cold characteristics are usually available for circuit breakers having ratings from a few
              amps up to 500 amps. For a given frame size it is usually possible to fit different ratings of thermal
              elements. Each rating of a thermal element has a narrow or nominal current, see Figure 12.20.


              12.8.2 Instantaneous or High-Set Overcurrent


              The necessity for an instantaneous tripping function is the same as for a high voltage motor. This
              function can be provided by a magnetic repulsion device within the moulded case circuit breaker, by
              a (50) relay or by upstream fuses. If fuses are used then the contactor must be capable of carrying
                  2
              the I t duty until the fuse completes its function. To minimise the stressing of the contactor it should
              be coordinated with the fuses as recommended in IEC60947 Part 2, as a Type 2 requirement.
                    The range of settings for moulded case circuit breakers is typically between 5 and 30 times the
              nominal current. The lower values e.g. 5, 7.5 and 10 are often fixed for a particular circuit breaker,
              whilst the higher values are adjustable.


              12.8.3 Negative Phase Sequence

              The purpose of negative phase sequence protection is the same as for high voltage motors. It is
              not normally needed for motor ratings less than approximately 22 kW. In the simpler designs of
              moulded case circuit breakers and relays the negative phase sequence detection is more in the form
              of single-phase protection, wherein a phase is completely lost.
   352   353   354   355   356   357   358   359   360   361   362