Page 578 - Handbook of Electrical Engineering
P. 578

CALCULATION OF VOLT-DROP IN A CIRCUIT CONTAINING AN INDUCTION MOTOR      571

               Hence the terminal voltage of the generator V gs is:-

                                 E o Z ogs  (1.0687 + j0.1068)(0.3631 + j0.6375)
                           V gs =      =
                                 Z gn s            0.3838 + j0.8892
                              = 0.8151 − j0.0087 pu, which has a magnitude of 0.8152 pu.

               Similarly the voltage of the MCC V ls is:-

                                         (0.8151 − j0.0087)(0.3050 + j0.7874)
                                V gs Z ols
                           V ls =      =
                                 Z cn S           0.3114 + j0.8418
                              = 0.7660 − j0.0199 pu, which has a magnitude of 0.7669 pu.
               Similarly the motor voltage V ms is:-

                                               (0.7660 − j0.0199)(0.2390 + j0.9257)
                                  V ls Z msl
                           V ms =          =
                                 Z msl + Z cm  0.2390 + j0.9257 + 0.00844 + j0.003175
                              = 0.7626 − j0.0140 pu, which has a magnitude of 0.7627 pu.

            n) Calculate the percentage volt-drops
               The customary method of defining volt-drop is in percentage terms as follows:-

                                              No-load voltage − Loaded voltage
                           Volt-drop in percent =                           × 100%
                                                      No-load voltage
                    Where the no-load voltage is the service voltage that exists before the change in load is
              applied and the loaded voltage is the service voltage during the application of the change in
              load. For example, when a motor is being started there are two aspects to consider. Firstly, the
              situation at the motor terminals since this determines the ability of the motor to create enough
              torque during the starting period and, secondly, at the MCC since this influences the performance
              of existing loads and their contactor coils. Other parts in the power system could be examined in
              a similar manner, e.g. at the generator terminals and its switchboard. The motor example above
              may be used to illustrate these comments:-
              • Motor terminal volt-drop in percent.
                 No-load voltage = pre-disturbance voltage at the MCC.
                 Loaded voltage = voltage at the motor terminals at starting or running of the motor.

                                                   V lo − V ms
                              Volt-drop at starting% =      × 100%
                                                      V lo
                                                   0.9936 − 0.7627
                                                 =                × 100% = 23.24%
                                                       0.9936
                                                   V slo − V mn
                              Volt-drop at running% =        × 100%
                                                      V lo
                                                   0.9936 − 0.9552
                                                 =                × 100% = 3.86%
                                                       0.9936
   573   574   575   576   577   578   579   580   581   582   583