Page 602 - Handbook of Electrical Engineering
P. 602

EARTHING CURRENT AND ELECTRIC SHOCK HAZARD POTENTIAL DIFFERENCE       595

                        Table H.1d.  Results for earth resistance, touch voltage, ground potential rise
                        and corner mesh voltage for different grid and rod designs
                        Case     R ep     E touch50  GPR      E m      I fe     I f
                        A.1      4.421      361      4796     1214    1085     1217
                        A.2      3.716      361      4133      914    1112     1229
                        A.3      3.215      361      3638      613    1132     1238
                        A.4      2.838      361      5254      509    1147     1245
                        A.5      2.544      361      2947      412    1158     1250
                        A.6      2.307      361      2694      343    1168     1254
                        B.1     44.13      1190     16,842    4271     382      929
                        B.2     37.11      1190     16,161    3580     435      947
                        B.3     32.12      1190     15,523    2618     483      964
                        B.4     28.37      1190     14,936    2338     526      980
                        B.5     25.43      1190     14,382    2009     565      995
                        B.6     23.07      1190     13,862    1766     601     1008
                        C.1     21.33      1190     13,431    3069     630     1020
                        C.2     18.59      1190     12,644    2953     680     1040
                        C.3     16.58      1190     11,968    1854     722     1057
                        C.4     15.02      1190     11,373    1808     757     1072
                        C.5     13.76      1190     10,841    1541     788     1085
                        C.6     12.71      1190     10,360    1351     815     1097
                        D.1     19.28      1190     12,856    3250     667     1035
                        D.2     16.92      1190     12,087    3103     715     1054
                        D.3     15.17      1190     11,433    1936     754     1071
                        D.4     13.80      1190     10,861    1879     787     1085
                        D.5     12.69      1190     10,351    1595     816     1097
                        D.6     11.76      1190     10,043    1394     841     1108
                        E.1     19.24      1190     12,947    3408     678     1035
                        E.2     16.88      1190     12,073    3286     715     1054
                        E.3     15.14      1190     11,421    2068     754     1071
                        E.4     13.78      1190     10,851    2022     787     1085
                        E.5     12.67      1190     10,343    1729     816     1098
                        E.6     11.75      1190      9884     1521     841     1109




           It is also necessary to relate the corner mesh voltage E m to the ground potential rise GPR of the grid
           and rod system.
                                        GPR = I fe R ep = 11967.9 volts


           Hence expressing E m as a percentage (E mpc ) of the GPR gives:-


                                                E m × 100
                                         E mpc =         = 15.49%
                                                  GPR
   597   598   599   600   601   602   603   604   605   606   607