Page 327 - Handbook of Energy Engineering Calculations
P. 327

reduces the amount of insolation, requiring a larger collector area to produce
               the  required  heating  or  cooling.  ASHRAE  also  publishes  tables  of  the
               average  percentage  of  sunshine  for  use  in  the  relation  for  determining  the
               actual solar insolation for a given location.


                          TABLE 3 Solar Position and insolation Values for 48°N latitude*



















               COLLECTOR  SIZING  FOR  SOLAR-ENERGY  HEATING

               SYSTEMS FOR BUILDINGS



               Select the required collector area for a solar-energy heating system which is
               to supply 70 percent of the heat for a commercial building situated in Grand

               Forks, MN, if the computed heat loss is 100,000 Btu/h (29.3 kW), the design
               indoor temperature is 70°F (21.1°C), the collector efficiency is given as 38
               percent by the manufacturer, and collector tilt and orientation are adjustable
               for maximum solar-energy receipt.



               Calculation Procedure:


               1. Determine the heating load for the structure
               The first step in sizing a solar collector is to compute the heating load for the
               structure. This is done by using the methods given for other procedures in
               this handbook in Sec. 13 under Heating, Ventilating and Air Conditioning,

               and  in  Sec.  13  under  Electric  Comfort  Heating.  Use  of  these  procedures
               would  give  the  hourly  heating  load—in  this  instance,  it  is  100,000  Btu/h
               (29.3 kW).
   322   323   324   325   326   327   328   329   330   331   332