Calculation Procedure:


               1. Determine the heat transferred in the heat exchanger
               Use the relation, heat transferred, Btu/h = (flow rate, lb/h)(outlet temperature
               –  inlet  temperature)  (liquid  specific  heat)(1.8  to  convert  from  °C  to  °F).
               Substituting for this heat exchanger, we have, heat transferred = (32,800)(90

               –  45)(0.9)(1.8)  =  2,391,120  Btu/h  (2522.6  kJ/h).  This  is  the  rate  of  heat
               transfer from the hot fluid to the cool fluid.


               2. Find the shellside outlet temperature
               The temperature decrease of the hot fluid = (rate of heat transfer)/(flow rate,