Page 449 - Handbook of Energy Engineering Calculations
P. 449

Fouling, Eq. (12):









                  Plate, Eq. (10):









                  Sum of Products (SOP):
                                SOP = 0.848 + 0.927 + 0.050 + 0.052 = 1.877(18.6m)

                  Because SOP is greater than 1, the assumed heat exchanger is inadequate.
               The surface area must be enlarged by increasing the plate width or the plate
               length. Because, in all equations, L applies directly, the following new length
               is adopted:

                                                    1.877 × 32.5 = 61 ft


               5. Compute the pressure drops in the hot and cold sides
               Hot side, Eq. (15):









                  Cold side, Eq. (15):












                  Because the pressure drop is less than the allowable, the spacing can be