Page 151 - Hybrid-Renewable Energy Systems in Microgrids
P. 151

Study of control strategies of power electronics during faults in microgrids    135

                 ref
                        ref
           where f  and V  are the frequency and voltage amplitude references for the volt-
           age control loop; while m and n are the slops of the droop characteristics; P meas  and
           Q meas  denote the measured active and reactive power delivered by the converter. In
           Fig. 7.9C, virtual impedance is used to modify the voltage references originally gener-
           ated by the droop characteristics [5]. This is another typical way of forming voltage
           amplitude reference, where the virtual impedance emulates the role of the impedance
           of a synchronous generator.


           4.2  Negative-sequence component control
           As discussed in Section 3.3, the control structure in Fig. 7.8 may cause unsatisfactory
           performance under unbalanced conditions due to the coupling between positive- and
           negative-sequence synchronous reference frames. To improve the VSI performance
           under unbalanced faults, the control structure of Figs. 7.8 and 7.9C is modified by
           only using positive-sequence signals. Regarding the voltage formulation, notch filters
           are used to eliminate the oscillations of the measured active and reactive power. In
           addition, a negative-sequence control loop is implemented in parallel with the control
           diagram of Fig. 7.8 as the main task of the converter is to regulate the voltage and fre-
           quency of the islanded microgrid, the various control strategies described in Section 3
           cannot be easily applied here. Therefore, the current references in negative-sequence
           are simply set to zero, which means the VSI will inject balanced short circuit current
           under unbalanced faults. As there is no negative-sequence current injected under fault
           conditions, the current limitation expressed by Eq. (7.38) can be used. Finally, the con-
           trol diagram with negative-sequence control loop implemented is given in Fig. 7.10.































           Figure 7.8  Basic control structure of a VSI operating in islanded mode.
   146   147   148   149   150   151   152   153   154   155   156