18   Improving Machinery Reliability

                                            PROCEDURE  FOR  COMPRESSOR  R U E
                       m.                      LUBE  AND  SEAL  OIL  SYSTEM


                                I  MACHINE TAG NO.   vc-01


                                     -  Time  for  "C"  to auto-start.
                                                               Sec.
                                     -  Minimum  oil pressure-vm on  compressor  deck
                                      Instrument Rack.
                                     -  Verify  V-CT-01  motor  control  does  not  trip.
                                     -  Minimum  level  obtained  in oil  accumulator.
                                  e.   Bleed pressure  off  the  lube oil  alarm  switches.
                                     VP046-LA  should  annunciate  at  15  psig.
                                                 Alarms  at  Local  Panel
                                                               MAPS   _I__-
                                        VXOLO-CA  alarms  at Control Center
                                     VP047LLA  should  annunciate  at  13  psig. __   -
                                                 Alarms  at  Local  Panel   -
                                                               MAP'
                                        VXOZO-CA  alarms  at
                                  f.  Bleed pressure  off  seal
                                     VP041-LA  should
                                                         ,oca1  Panel
                                                               MAPS  _____
                                              3'     at  Control Center
                                ''          .nould  annunciate  at  25 psig.
                                                  Alarms  at  Local  Panel
                                                               MAPS
                                        VX021-CA  alarms  at  Control Center
                                     VP077-LA  should  annunciate  at  15  psig.
                                                  Alarms  at  Local  Panel
                                                               MAPS
                                        VX021-CA  alarms  at  Control  Center
                                     VPO78LLA  should  annunciate  at  15  psig.
                                                  Alarms  at  Local  Panel
                                                               MAPS
                                        VX021-CA  alarms  at  Control  Center  ----I




                          DATE                                           FILE REFERENCE
                                       MACHINERY RELIABILITY PROGRAM     13-2-6.1
                        1211 2/97                                        Section 201

                                  Figure 1-10. Typical instrument checkout guidelines.