Page 208 - Industrial Power Engineering and Applications Handbook
P. 208

7/188 Industrial Power Engineering and Applications Handbook
              In  HT motors  the terminal  box  for space heaters   impedance, because of the saturation effect, than at a reduced
              and  embedded  temperature  detectors  must  be   voltage. The Zst at full voltage therefore would  be  slightly
              separate from the main terminal box.           higher than that calculated from the starting current, measured
              The terminal box must be capable of  withstanding   at a reduced voltage. Hence the allowance for this. See also
              the system fault current for at least 0.25 second.   Figure 27.2(b).
              The terminal box must be suitable for being turned
              through  180”, for bottom or top cable entry.   10 Frequency of start: The HT motors must be suitable
              The terminal  box  must  have  the  same degree of   for two starts in quick succession when the motor is
              protection as the motor.                     hot or three equally spread starts in an hour (not to be
              For large motors,  1000 kW and above, if they are   repeated in the second successive hour).
              provided with  star windings the three neutral end   11 Stresses during a fast bus transfer: A fast bus transfer
              leads must be connected to a separate terminal box   between the unit and station supplies is an essential
              to enable mounting of CTs for differential protection.   feature in a power station to maintain an uninterrupted
              The  neutral  terminal  box  need  not  be  phase   power supply to the unit and station auxiliary services
              segregated.                                  (Figure  13.21). The  changeover  may  be  as  fast  as
          7  Performance                                   three or four cycles which is adequate to break before
              Motors must be designed for an ambient temperature   make in the modern interrupting devices and hence is
              of 50°C.                                     safe to adopt. The motors should, however, be suitable
              HT motors must be generally wound with class F   of withstanding excessive voltages on account of this
              insulation and the temperature rise should not exceed   up to 150% of the rated voltage for at least one second
              the prescribed limits of class B insulation. LT motors   during such bus transfers.
              up to 250 kW, however, can be wound with class B
              insulation.                                  Nure  The time gap between a fast bus transfer is so small that
              The performance  of  the  motors  must  conform  to   it will not permit the various drives to slow down sufficiently to
              IEC 60034- 12.                               affect their performance  or the system if  they  are made to re-
          8  Voltage and frequency variations              accelerate (reenergize) on restoration  of power.
              During  start-up,  the  motors  must  be  suitable for
              accelerating to 80% of the rated voltage.    In  a  fast  bus  transfer  scheme,  the  phase  angle  is
              Motors  must  run  at  full  h.p. under the  following   monitored through special relays (Section 16.1 1) which
                                                           initiate the changeover, so that the self-induced e.m.f.
              conditions:
              Variation in frequency: f5%                  of the motor does not slip too far in the phase angle,
                                                           A@, between  the two voltages  and the motor is not
              Variation in voltage: flO%
              Combined variation in frequency and voltage: f10%   exposed to excessive overvoltages. At higher A6 the
              Motors must not stall due to a momentary  dip in   relays will block the transfer and protect the system
              voltage up to 70% of the rated voltage, i.e.   from excessive voltages. If the fast bus transfer fails
                                                           to change over automatically, slow changeover takes
              7’  to be  more  than  T,./(0.625)’,  i.e.  256%  for a   place and the motor-induced e.m.f. is allowed to decay
              1200 r.p.m. motor and TJ(O.605)’,  i.e. 273% for a   by up to 40-20%  before the bus transfer takes place.
              1000 r.p.m. motor and less, as shown in Table 1.5.
              Motors  must run  satisfactorily for 5  minutes  at  a   For  insulating  and  bracing  the  windings,  such  bus
                                                           transfers may occur up to 500 times in the total lifespan
              supply voltage of  75% of the rated value.
                                                           of the motor.
                                                         12 Starting time and locked rotor withstand time
              Nore  This operating condition is, however, not specific for   For motors with a starting time of up to 20 seconds,
              it does not stipulate the frequency  of  occurrence  of  such a   with  the  minimum  permissible  applied  voltage
              contingency. It may be assumed that this condition will not
              occur more  than  once before  thermal  stability is  reached.   (80%), the locked rotor withstand time under hot
              See also Section 3.7. In normal practice a motor meeting the   conditions  at  rated  voltage  must  be  at  least  2.5
              other operating conditions noted above in all likelihood will   seconds more than the starting time.
              satisfy  this  requirement also  without  needing  yet  another   For motors  with  a  starting time  of  more  than  20
              derating. See also Example 7.1,                seconds  but  within  45  seconds,  at  the  minimum
                                                             permissible applied voltage (SO%), the locked rotor
          9  Starting current                                withstand time, under hot conditions at rated voltage,
              On DOL the I,, must not exceed 600% of I, but for   must be at least 5 seconds more than the starting time.
              boiler feed pumps it must be limited to 450% of I,,   13 Bearings: The bearings will preferably have an arrange-
              subject to the tolerance stipulated in IEC 60034-1.   ment for self-lubrication.
              To determine the starting current, when the test is   14 Bearings  must  be  insulated  wherever  necessary, to
              conducted  at  a  reduced  voltage  (1/&  Vr ),   prevent them from shaft currents (Section  10.4.5).
              allowance must be  made for the  saturation  effect   15 Over-speed:  Motors  will  be  designed  to  withstand
              while estimating the value of I,, at the rated voltage.   120% of  ff, for  at  least  2  minutes  without  any
              See also Section  1.6.2(A) also (the important note   mechanical damage.
              on starting torque).                       16 Noise level: Motors must conform to the requirements
                                                           of  IEC 60034-9. A  safe sound  pressure  level for a
              Note  At  full  voltage,  the  stator core  will  offer  a  lower   human  body  to  perform  better,  during an  8-hour
   203   204   205   206   207   208   209   210   211   212   213