Page 273 - Industrial Power Engineering and Applications Handbook
P. 273

11/252  Industrial Power Engineering and Applications  Handbook
                temperature measurement by thermometer when   11.3  Procedure for testing
                the machine is hot.
          3  Load test                                 In the following we describe a brief procedure to conduct
          4  Overspeed test                            various tests and measurements and computation of the
          5  Speed-torque  and speed-current  curves   test results according to IEC 60034-1. (For more details
          6  Vibration  measurements  and  noise  level  tests  to   of  the testing procedure the reader  should refer to the
            determine the machine’s mechanical performance
          7  Verification of dielectric properties     standard.)
             (i)  On the completed machine with wound coils or
                formed coils: power frequency voltage withstand   11.3.1 Resistance measurement
                or HV test                             At the beginning of the test the motor must be at ambient
            (ii)  Process tests during the manufacture of formed   temperature.  In  this  condition  the  temperature  and
                coils                                  resistance of the windings should be recorded accurately.
            (a)  Test  for insulation  resistance  - discussed  in   These values will be used later, with other test results, to
                Section 9.5.3                          evaluate the temperature rise and efficiency.
            (b)  Test for dielectric loss factor or dissipation factor   Many types of winding connections are used, depending
                tan Gfor rated voltages 5 kV and above   upon the type of machine and the application for which
            (c)  Test  for  impulse  voltage  withstand  for rated   it is designed. The basic star and delta connections are
                voltages 2.4 kV and above.             most common, but a combination of these two with parallel
                                                       circuits  is also  used,  on  multi-speed  and  dual-voltage
            Note                                       motors,  as  discussed  in  Section  6.1.  The  connection
            1  The impulse voltage test is meant specifically for formed   diagram of  the  motor,  showing the connections of  the
               coils only.  It  serves  no  purpose  for  a  wound  machine,   windings and the terminal arrangement, should also be
               which is already impregnated and cured as a whole mass.
            2   The tests for insulation resistance and dielectric loss factor   checked for correctness of  the connections. Resistance
               should, however, be carried out on a completed machine   across  the  line  terminals  of  the  windings  should  be
               also with formed coils to establish reference data for field   measured, except for a star-connected motor, where phase
               tests, as noted  in  Section 9.6. However,  these tests on a   resistance is measured.
               completed machine with formed coils do not monitor the   Typical connections are shown in Fig.  11.2, where
               process  quality of insulation.
                                                        R1 = e R, in star-connected windings, and
          8  No-load test                                   2i
          9  Locked rotor test
                                                            3
                                                                e
         10  Measurement of starting torque, pull-out torque and   R1 = - x - R  in delta-connected windings.
            pull-in torque                                  2   i
         11  Open-circuit voltage ratio test for slip-ring motors   The  following  two  methods  are  commonly  used  for
         12  Verification  of degree of protection.    measurement of winding resistance.
         11.2.3 Routine tests                          The drop of potential method or voltmeter-
                                                       ammeter method
         Routine  tests  are  conducted  on  subsequent  similar
         machines. The purpose of  a routine test is to ascertain   In this method simultaneous readings of voltage at motor
         that the machine is assembled correctly and will be able   terminals and current are taken while using a d.c. source
         to withstand the appropriate high-voltage test, and will   of supply and the resistance of the windings is calculated.
         be  in  sound  working  condition,  both  electrically  and   Current must be restricted to 10% of the rated current of
         mechanically. As a minimum requirement these tests will   the windings.  Errors introduced  into the measurement,
         consist of                                    by the resistance of leads and contacts must be compen-
                                                       sated.
         1  Resistance measurement
         2  No-load test
         3  Verification of dielectric properties
         4  Insulation resistance test                                                     i
         5  Measurement of open-circuit rotor volts for slip-ring
           motors.

         11.2.4 Seismic disturbances
         We provide a brief account of such disturbances in Section
         14.6. This  also deals  with  the recommended  tests  and                     Rl
         their  procedures  to  verify  the  suitability  of  critical   (a) Y-Connected   (b) A-Connected
         structures, equipment and devices for locations that are
         prone to such disturbances.                        Figure 11.2  Measurement of winding resistance
   268   269   270   271   272   273   274   275   276   277   278