Page 618 - Industrial Power Engineering and Applications Handbook
P. 618

Voltage surges-causes,  effects and remedies  17/583

                          R  Y  B                    17.10.6  Conclusion
                          1  1  1
                                                     Switching  of  an  induction  motor  was typical  of  all  to
                                                     illustrate  the  pheno-menon  of  switching  surges  in  an
                                                     inductive circuit. The situation would remain the same
                                                     when switching  a power  system, transformer  or power
                                                     cables  also,  in  all  conditions  of  loading  (fully  loaded,
                                                     under  loaded  or  on  no  load).  Switching  surges  in  a
                                                     capacitor circuit is discussed in Section 23.5.1 with the
                                                     likely  levels  of  voltage  surges.  Below  we  discuss  the
                                                     insulation coordination and protection of other machines
                                                     and systems.

                                                     17.11  Theory of surge protection
                                                             (i nsu lat ion coordination)

                                                     The insulation of a current-carrying  system, machine or
                                                     component is to provide it with the required insulation
                                                     level (BIL) to withstand system voltages during normal
                                                     operation, as well as temporary overvoltages (TOV) and
                                                     momentary voltage surges, up to a certain level, during
                                                     system disturbances. A safety margin is built into their
                                                     equipment by the manufacturers according to Tables 11.6,
                                                     14.1, 32.1(A), or  13.2 and  13.3 as standard practice  to
                                                     sustain such  voltages  without  failure or rupture  of  the
       Figure 17.24(a)  C-R-   Figure  17.24(b)  Typical  power   insulating system. Repeated application of such voltages,
       type surge suppressor   circuit of a C-R-type surge suppressor
                                                     even if they are below the BIL of the insulating system,
                                                     or longer duration  of  overvoltages,  may lead to failure
                                                     or rupture of the insulating system as a result of insulation
       surge, a low resistance path, and a means of absorbing
      the excess energy of the surge to dampen it to a required   fatigue. It is possible that in operation, TOVs or voltage
                                                     surges may exceed the safe (prescribed) power frequency
      level while the surge capacitor arrests the  steepness of   or impulse withstand voltages (BIL) respectively, of the
      the surge and reduces it to a desired r.r.r.v.   power  system  or  the  terminal  equipment.  For  the
        The  design  of  the  C-R  combination  maintains  a
      negligible level of leakage current through the suppressor   recommended  safe insulation  levels of different equip-
                                                     ment, refer to tables mentioned  above.
      in healthy  conditions  (to contain  resistance loss).  It  is   For instance, when lightning of, say, a nominal discharge
      easily  achieved,  as  C provides  a  near-open  circuit  in   current of  10 kA strikes a 400 kV (r.m.s.) overhead line,
      these conditions and permits only a very small leakage   having  a surge impedance of  350 Q, then  two parallel
      current to flow through it.                    waves will be produced each of amplitude 10 x 350/2 or
        A  C-R  suppressor  also  helps  to  reduce  the  surge
                                                     1750 kV which may be more than the impulse withstand
      impedance, Zs, of the circuit and thus limits the amplitude   level  of  the system and cause a flashover between  the
      of  Vt as discussed in Section  17.8.
                                                     conductors  and the  ground, besides  damaging  the  line
                                                     insulators and the terminal equipment (Table 13.2). It is
      Note                                           therefore imperative that the system is protected against
      Since a  surge capacitor or a  C-R  combination surge suppressor   such eventualities.
      operates only at very high frequencies, such as those related to an
      FOW, they maintain a near-open circuit for the arriving long-duration   Surge protection, therefore, becomes essential when it
      switching surges. They are thus required to handle only a moderate   is felt that the surges generated during an operation at a
      amount energy of an FOW and hence are suitable for such duties.   particular  installation  may rise beyond the permissible
                                                     impulse withstand  capacity  (BIL) of  the equipment. A
      17.10.5  Setting fast-responding relays        system that is prone to frequent occurrences of temporary
                                                     overvoltages. Induction motors for instance, which conform
      No system is permitted  to trip  on the occurrence of  a   to the impulse withstand levels prescribed for this machine
      momentary disturbance, such as by travelling  surges of   according to Table 11.6 may be supplemented by a surge
      any kind. To overcome this:                    arrester or suppressor, when it is felt that the amplitude or
                                                     steepness (or both) of the surges in operation may exceed
        The  motor  protection  relay,  as discussed  in  Section   the prescribed  levels. Coordination  of  insulation  of  the
        12.5, is  generally  provided  with  a  delay  feature  to   equipment to be protected  with that of  the level of  the
        bypass these transients and delay the tripping by two   protectivedevice, whichmay be a switchgear or alightning
        or three cycles.                             arrester,  is called  insulation  coordination. This  would
        The same is true for an overcurrent or a ground fault   depend upon the type of installation, such as the type of
        relay when used in circuits that are prone to surges.   switching  device and the length  of  the interconnecting
   613   614   615   616   617   618   619   620   621   622   623