Page 878 - Industrial Power Engineering and Applications Handbook
P. 878

26/830 Industrial  Power Engineering  and Applications Handbook
          up to 150% of the rated current continuously and operate   Protection  with  internal  fuses  is  easier,  as  fuses  are
          for a few seconds at 300%. Refer to Figure 2 1.4 for   provided for each element which can contain the severity
          typical current-time  curves of HRC fuses. Use of an   of the fault well  within  the safe zone in all probability.
          IDMT relay  with an appropriate  setting will  also be   Some users  even  recommend  capacitor  units  250/300
          good practice in such cases.                 kVAr  and  above with  internal  fuses  only.  Figure  26.1
          For-delta  connected  capacitor  units:  In  this  case,  it   shows a typical operating band of the internal fuses for
          will  establish  a  line-to-line  fault  with  a  heavy  fault   an internally protected unit.  It demonstrates a sufficient
          current.  Protection  by  HRC  fuses  would  be  more   margin between the operation of the fuses and the shell’s
          appropriate than for a grounded star or using an MCCB.   safe zone. The fuse characteristics are almost the same
          For series-parallel connected units: This is applicable   for all  manufacturers.
          in HT capacitor banks comprising a numher of small   Since such explosions are dangerous and may cause a
          units arranged in series and parallel combinations. The   fire  hazard through the dielectric liquid which  may be
          fault current in such cases for an isolated neutral can   inflammable, it is imperative that such faults are cleared
          be expressed by                              before they may result in bursting of the shell. They will
                                                       require short-circuit protection.  Leading manufacturers
           I,-=-.  3N,  Nl        (from equation (25.3))   producing units  suitable for external protection provide
               3N, -2  I‘                              a  pressure-sensitive  disconnector  which  operates  and
          Now  also  an  IDMT  relay  would  provide  the  most   releases  the  pressure  during  a  fault  when  the  inside
          appropriate protective scheme.               pressure builds up to a preset level. This may be in the
                                                       form  of  expandable  bellows,  which  expand  on  such
          To summarize, HRC fuses or fuse-free MCCBs for LT   excessive  pressures  inside  and  snap  open  the  power
         and a breaker and IDMT relay arranged for 2 O/C and   connections. Safety through expansion bellows is usually
         1 G/F, with a short-circuit unit for HT capacitor banks,   a feature in LT, MPP capacitors. In HT this technology is
         will provide a reliable protective scheme for short-circuit   not  used.  NEMA  has  also provided probability curves
         and ground fault protections.                 for the case rupture in the form of 1’  versus 1. The curves
                                                       are defined in Figure 26. I, which can be used to select
         6 Shell protection                            the appropriate protection to isolate the unit  on a fault
                                                       before a possible rupture. The severity of fault is expressed
         This is applicable to both LT and HT capacitors. But it is   in terms of the magnitude of explosion. The protection
         more important in HT banks, which are relatively  much   must be commensurate with the location and the criticality
         larger and are built of a number of single units connected   of  the  installation  and  is  categorized  in  four  zones,
         in series-parallel. These may encounter much higher fault   depending upon the severity of the fault:
         currents in the event of  a  severe internal fault, even  in
         one unit  and are thus rendered more vulnerable to such   1  Safe zone: There is only a slight swelling of the shell
         ruptures. This phenomenon  is more applicable to units   and no severe damage.
         that are externally protected where the intensity of fault   2  Zone I: There may be a slight rupture and fluid may
         may  be  more  severe,  than  internally  protected  units.   leak.  Safe for areas where the leakage will  pose no
                                                          hazard.
                                                       3  Zone 11: There may be a violent rupture of the shell.
                      Probability curves for case rupture
                            0.1   0.5   0.9            4  Hazardous zone: There may be a violent rupture with
                                                          a blast, which may damage the adjacent units.
                      I  Safe  I  Yqlt                 Note
                 10                                    The practice  adopted by  manufacturers, for all voltages and kVAr
                                                       ratings in the making of the shell, particularly  for its size, material
                                                       and thickness,  assume almost the same I‘  versus t characteristics,
                                                       as provided  by  the NEMA curves (Figure 26.1).
                                                         For a more accurate selection of a protective scheme it
               t  3’0                                   is essential that the manufacturers provide the probability
              -.  1.0                                  curves of their shell design for each voltage and rating.
               m
              E                                          Generally, the fault must he cleared well within Zone
               m                                        I and for which  the protective scheme must be chosen.
              E  0.3
                                                        As discussed  in  Section 25.4.2, protection of capacitor
                                                        units with external fuses is not easy. It is not practical  to
                                                       contain a mild  internal fault as isolation of the units is
                 0.1
                                                        not possible on mild internal faults until the fault current
                                                        rises to the  level  of  the fuse’s  operating range  (Figure
                        Fault current, amp (rms) -      26.2  illustrates  this).  By  then  enough  time  will  have
                   I   30   100   300   1000            elapsed to cause severe damage to the unit.
                                                         The only solution is to choose fuses of a lower rating
                                                        as far as possible, with fast operating characteristics (low
                Figure 26.1  NEMA’S case rupture curve   1*t) or provide IDMT protection. But the risk of a shell
   873   874   875   876   877   878   879   880   881   882   883