Page 71 - Industrial Process Plant Construction Estimating and Man Hour Analysis
P. 71

42  Industrial Process Plant Construction Estimating and Man-Hour Analysis


            2.5.3 Welding—SOL, TOL, and WOL
            Facility—Solar power plant

            Man-hour Per SOL, TOL, and WOL
                                      Wall thickness in inches
              Pipe
              size  0.375 or less 0.406 –0.500 00  0.562 –0.688 00  0.718 –0.938 00  1.031 –1.219  00
                                   00
                       00
                                              00
                                                          00
                                                                     00
              0.5      2.20       2.40        4.40       4.90        5.40
              0.75     2.20       2.40        4.40       4.90        5.40
               1       2.20       2.40        4.40       4.90        5.40
              1.5      2.20       2.40        4.40       4.90        5.40
               2       2.20       2.40        4.40       4.90        5.40
              2.5      2.50       2.75        5.25       6.00        7.25
               3       3.00       3.30        6.30       7.20        8.70
               4       4.00       4.40        8.40       9.60       11.60
               6       6.00       6.60       12.60       14.40      17.40
               8       8.00       8.80       16.80       19.20      23.20
              10       10.00      11.00      21.00       24.00      29.00
              12       12.00      13.20      25.20       28.80      34.80
              14       14.00      15.40      29.40       33.60      40.60
              16       16.00      17.60      33.60       38.40      46.40
              18       18.00      19.80      37.80       43.20      52.20
              20       20.00      22.00      42.00       48.00      58.00
              24       24.00      26.40      50.40       57.60      69.60
            SOL, TOL, and WOL welds; two times BW (includes cut, prep, and fit up).
            Wall thickness of the pipe used for olet determines man-hours that will apply.
            Apply percentages for welding alloys and nonferrous welds.