Page 81 - Injection Molding Advanced Troubleshooting Guide
P. 81

8.3 Velocity Linearity  65



          To determine if the problems stem from the non-return valve or a worn spot in the
          barrel try moving the shot size and transfer position back approximately 25 mm
          and doing the 10-shot study again. If the fill only weight variation is better after
          changing the shot size and transfer position there is probably a worn spot in the
          barrel that is causing the problem rather than the non-return valve.
          If a non-return valve appears to be an issue the end cap of the press should be
            removed  and  the screw tip  and  non-return  valve  should  be  inspected for  wear,
            damage, or contamination. If an issue is detected the non-return valve should be
          replaced.




          „ „8.3„ Velocity Linearity



          Processors often assume that the setpoint that they enter in a machine controller
          is what the machine will provide. A classic area where this may not be the case is
          velocity. To determine if the machine is providing the velocity that is requested
          follow these steps:
           1. Set the process to run a fill only shot, no second-stage pressure.
           2. Adjust transfer so that the part is approximately 80% full.

           3. Record shot size, decompression, and transfer position.
           4. Set the fill velocity to the minimal practical value.
           5. Record fill time.
           6. Double the velocity setpoint.
           7. Record fill time.
           8. Repeat steps 5–6 until machine maximum is obtained.
           9. Calculate the actual fill velocity for every step (Equation 8.4).
          10. Calculate percent difference for each velocity (Equation 8.5).
          11. Calculate the total range of fill difference by subtracting the minimum differ-
             ence from the maximum difference. Maximum range should be below 10%.
          Calculating actual fill velocity:


            ( shot size + decompression)− transfer position
                           fill time              =  actuall velocity       (8.4)


            set velocity − calculated velocity  = %  difference             (8.5)
                    set velocity
   76   77   78   79   80   81   82   83   84   85   86