Page 157 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 157
(a) This machine is a generator supplying real power to the power system, because E is ahead of V .
A
It is consuming reactive power because E cos V .
A
(b) This machine is acting as a generator, and the current flow in these conditions is
E V 430 15 440 0 V
I A 28.4 16.8 A
R A A jX S 0.3 j 4.0
The real power supplied by this machine is
P 3V I A cos 3 440 V 28.4 A cos 16.8 35.9 kW
The reactive power supplied by this machine is
Q 3V I A sin 3 440 V 28.4 A sin 16.8 10.8 kVAR
In other words, this machine is consuming reactive power.
(c) This machine is a motor consuming real power from the power system, because E is behind V .
A
It is supplying reactive power because E cos V .
A
(d) This machine is acting as a motor, and the current flow in these conditions is
V E 440 0 V 470 20
I A 40.1 4.9 A
R A A jX S 0.3 j 4.0
The real power consumed by this machine is
P 3V I A cos 3 440 V 40.1 A cos 4.9 52.7 kW
The reactive power supplied by this machine is
Q 3V I A sin 3 440 V 40.1 A sin 4.9 4.5 kVAR
In other words, this machine is supplying reactive power. It is operating within its rating limits.
151