Page 50 - Know and Understand Centrifugal Pumps
P. 50

Cavitation


       check valve  installed backwards, or operating  the pump  at or close to
       shut-off head.  Maybe a variable speed motor could help under certain
       circumstances.

      The vane passing syndrome
       The vane passing syndrome can exist when the blade tips at the OD of
        the impeller are passing too close to the cutwater on the pump casing.
       This  can  be  caused  by  exchanging  an  impeller  for  a  larger  diameter
       impeller, or from re-metalizing or coating the internal housing of  the
       pump. The free space between the impeller blade tips and the cutwater
       should be 4% of the impeller diameter (Figure 3-3).
       With the pump disassembled on the shop table, the damage is seen on
       the blade tips at the OD of the impeller, and just behind  the cutwater
       on the internal volute wall.
       For a 13“ impeller, the free space should be 4% of the impeller diameter
       between the blade tips and the cutwater.

                                13” x 0.04 = .520”
        On  a  13”  impeller,  there  should  be  at  least  a  half-inch  free  space
        between the blade tips as they spin past the pump cutwater.


      Air aspiration
       Air  can  be  drawn  into the  piping  and  pump  from  diverse forms and
       different  points.  Air  can  enter  into  the  piping  when  the  pump  is  in
       vacuum. An example of this is a lift pump. Lift pumps tend to lose their
       prime and aspirate air into the suction piping and pump.
        1.  The air can come into the pump through:
           w  The pump shaft packing.

           w  Valve stem packings on valves in the suction piping.
















                                                     syndrome
      Figure 3-3
      ~.    .
   45   46   47   48   49   50   51   52   53   54   55