Page 297 - Mathematical Models and Algorithms for Power System Optimization
P. 297

Local Decoupling Control Method for Transient Stability of a Power System 289

               calculation only based on local measurements, by which norm reduction control criterion is
               derived for local stability control. The control criterion consists of local observable decoupled
               state variables, so it requires local feedback only. Theoretically, if the operation mode exists
               after the fault happened, and the system could make each local stability control always meet the
               norm reduction control criterion in an online manner, the overall system is asymptotically
               stable in the sense of Lyapunov.

               8.2.3 Two Stage Countermeasures in Local Stability Controls

               In summary, the countermeasures in local stability control in emergency situations can be
               divided into two stages:

               In the first stage: Implement emergency control over the instability of local single generator in
               the first swing period, so as to brake the synchronous generator, which is required to estimate or
               determine the excess energy obtained during the fault as soon as possible, so as to withdrawal or
               absorb the excess energy.

               To achieve this, the switching of the braking resistor is desirable because it has a certain degree
               of fastness and the required flexibility for the operation. In addition, fast valve can also be
               considered if it can be opened and closed quickly enough.

               It is known from the equal area criterion that when the sum of the energy absorbed during the
               braking period and the excess energy obtained during the fault period is zero, then the impact of
               switching off the brake on the subsequent oscillation is minimal. Therefore, this criterion can be
               carried out for the first stage control. Because this criterion is based on the energy equilibrium,
               it can be called the first stage control criterion (energy equilibrium).
               In the second stage: Control multiple swings of multiple generators in each part of the
               system by following the norm reduction control criterion, based on no loss of synchronism of
               the local single generator in the first swing at the first stage. Because this criterion is based
               on the value of critical power, it can be called the second stage critical power control
               criterion.

               However, it should be pointed out that, in the actual local stability control of the system, it is
               difficult to rigidly meet the norm reduction control criterion because the value of critical power
               needs to be calculated online and is thus time-varying. Furthermore, the actual control measures
               based on the critical power value could be only switched on and off in a step-wise form in
               general.

               In addition, the norm reduction control criterion requires that each part of the system must be
               controlled in line with the derived respective criterion value. To this end, even if it is not
               difficult, it will be costly, so only a limited number of stability control devices are set at several
               critical local parts for the actual system.
   292   293   294   295   296   297   298   299   300   301   302