Page 298 - Mathematical Models and Algorithms for Power System Optimization
P. 298

290 Chapter 8

            Therefore, in the course of actual control, it is necessary to rely on the norm reduction control
            criterion as much as possible. As a matter of fact, it is sufficient to achieve this as far as
            possible because strict conformance with the norm reduction control criterion is a sufficient
            condition for overall system stability rather than a necessary condition. The simulation
            calculation for the analog system indicates that, as long as the criterion is met as much as
            possible, system stability will be satisfied.
            In addition, it should be pointed out that, to simplify the calculation and better describe the
            problem, the simplest models are used in both theoretical analysis and system simulation
            calculation, the problems are idealized, and less technical details involved in realization are
            considered. Theoretically, it will not affect the effectiveness of the conclusion, and it could
            liberate us from numerous minor details. This is more favorable to the problem to be
            clarified.



            8.3 Basic Concepts of Control Criteria based on Local Control

            To describe the physical background and requirements of transient stability control, a
            simplified mathematical model and typical network of power system is given in Section 8.3.1;
            the control countermeasure adopted for the power system is divided into two stages (emergency
            and norm reduction), which are described in Sections 8.3.2–8.3.3.



            8.3.1 Simplified Model and Typical Network of the Power System

            To describe the idea how to solve the problem mentioned in Section 8.2, a power system
            network model with N buses is provided, as shown in Fig. 8.1.

            In Fig. 8.1,{U i , α i } is the voltage and phase angle of bus i,{Z ij , φ ij } is the impedance value
            and phase angle of line i-j, X C is one-half the capacitive reactance of line i-j,and {P Li , Q Li }
            is the load. In addition, within the dotted line are generator bus parameters, {E i , δ i }is the
                                                                                     0
            internal electromotive force and phase angle of the generator, P mi is the generator input
            power, P Di is the generator damping coefficient, J i is the rotary inertia of generator rotor,
               0
            X di is the transient reactance of the generator, and u i is the controlled quantity imposed on
            the generator bus i. Obviously, there is no parameter for the passive bus within the
            dotted line.

            The electromechanical equation of the power system for the network in Fig. 8.1 is as follows:
            (1) Rotor motion equation:

                                               0
                                              E U i
                              €
                                     _
                             J i δ i + P Di δ i  P mi +  i  sin δ i  α i Þ + u i ¼ 0 i 2 1, NŠÞ  (8.1)
                                                                     ð
                                                                        ½
                                                     ð
                                               X  0
                                                di
   293   294   295   296   297   298   299   300   301   302   303