Page 135 - Modern Control of DC-Based Power Systems
P. 135

Background                                                    99


                                  V



                                  V 0
                                                     R 2

                                                    R 1
                                         I 2  I 1         I
              Figure 3.8 Two parallel voltage sources with different operating points at different
              droop steepness characteristics.

                 The voltage V and current I are the output voltage and the output
              current, V 0 is the nominal voltage and R is the gradient of the droop
              characteristic, which is physically equivalent to a resistor and is therefore
              referred to as such.
                 There are different possibilities to realize the droop control with a
              control system [7 9]. Here the current I is defined as the output variable
              and voltage V as the input variable of the control system, since the current
              can be easily controlled with DC/DC converters.
                 The deviation of the output voltage from the nominal voltage V 0  V
              means that the transfer function of the controller can be written as:
                                           I      1
                                                5                        (3.26)
                                        V 0 2 V   R
                 This corresponds to a proportional controller with the gain factor
                  1
              K 5 .
                  R
                 Since a proportional controller always has a permanent control devia-
              tion, a proportional integral controller (PI controller) can also be used.
              However, it must be kept in mind that with PI controllers connected in
              parallel, the start value of the control deviation has a large influence on
              the control due to the integrating part. As a result, the stationary state of
              the control system depends on the control parameters, the line resistances
              and the noise. This is reflected by unevenly distributed load flows. To
              avoid this problem, only one PI controller should be implemented in the
              control system, the others should be kept as P controllers. It should also
              be noted that the combined voltage and current control systems have
              defined stationary states, even when using PI controllers, as these control
              methods regulate both the current (or power) and the voltage, as the
              name suggests. The block diagram of a generator with voltage droop con-
              trol is shown in Fig. 3.9.
   130   131   132   133   134   135   136   137   138   139   140