Page 244 - Modern Control of DC-Based Power Systems
P. 244
208 Modern Control of DC-Based Power Systems
Figure 5.67 Voltage virtual distribution sliding mode cascaded Ideal CPL Step
10.3 - 17.8 MW.
Figure 5.68 Current virtual distribution sliding mode cascaded Ideal CPL Step
10.3 - 17.8 MW.
t 5 0.25 s the load step of 7.5 MW was performed, demonstrating that
the SM control is able to stabilize the system towards the voltage refer-
ence V ref 5 1: The dynamic of the inductor current is described in
Fig. 5.68.
In order to better clarify the effect of the parameter β previously
defined, the phase plane plot of the cascaded simulation is described in
Fig. 5.69.