Page 103 - Offshore Electrical Engineering Manual
P. 103

90     CHAPTER 7  DC Switchgear




                         dangerous situation of the arc remaining unquenched, outside the chute. Modern
                         circuit breakers are designed to avoid this condition.
                            Typical DC loads and fault currents are highly inductive, and circuit breakers
                         must be capable of dissipating all the energy stored in the circuit until arc extinction.
                         Such highly inductive loads will maintain the arc for longer whilst the stored energy
                         in the load circuit decays. This will place more stress on the contacts, so two-stage
                         contacts are now used, where the magnetic coils ensure that the arcing contacts take
                         the onerous arcing duty whilst the main contacts will carry the load current when the
                         circuit breaker is in the closed position.
                            All  circuit  breaker  mechanisms  (including  alternating  current)  should  be  ‘trip
                         free’, i.e., if a fault occurs during closure (making fault), the tripping action must
                         still be available and the circuit breaker does not need to close first. Obviously, once
                         the circuit breaker is closed and latched, all necessary protection device trips must
                         still be operationally live. Trip circuit supervision should be provided, where the trip
                         circuit continuity is monitored and provided with an alarm facility in a manned area.
                         Fig. 2.7.1 shows a typical modern DC circuit breaker.
                            Other arc quenching methods may be used.

                          •   ‘Arc runners’ will assist with avoidance of critical current by leading the
                            arc away from contacts, also driven by electromagnetic forces from blowout
                            coils.
                          •   A ‘puffer’ stream of air may be used to assist moving the arc into the arc
                            chute.



                         SPECIFICATION

                         Modern DC circuit breakers should be specified for

                          •   rated voltage and impulse voltage,
                          •   maintaining dielectric strength,
                          •   rated switching current for load and overload,
                          •   trip time performance, i.e., high speed, and current limiting,
                          •   current sensing – directional or bidirectional,
                          •   thermal performance for continuous rated current,
                          •   fault performance, i.e., arc containment of pressure/safe venting of gasses and
                            heat dissipation.

                         Variable-frequency inverter drives are covered in PART 2 Chapter 11.
   98   99   100   101   102   103   104   105   106   107   108