Page 98 - Offshore Electrical Engineering Manual
P. 98

Parallel Operation  85




                                                            OVER COMPOUNDED

                                                                       RATED VOLTAGE

                                                            FLAT COMPOUNDED
                    VOLTAGE                                 UNDER COMPOUNDED





                                                            FULL LOAD



                                                AMPERES
                  FIGURE 2.6.3
                  Compounding characteristics.



                  ADJUSTMENT OF COMPOUNDING
                  Voltage characteristics may be modified by adjusting the airgap during manufactur-
                  ing by inserting or removing shims between the poles and the yoke. Other methods
                  are

                   •   the use of a diverter resistance connected in parallel with the series winding,
                   •   adjustment of the commutator brush position.

                     The shunt field may be connected in ‘short shunt’ (Fig. 2.6.1A) or ‘long shunt’
                  (Fig. 2.6.1B). The effect on the characteristics is usually minimal, but machines
                  should always be operated as originally built. In small generators, the effects of
                  armature reaction are reduced by actually mechanically shifting the position of the
                  brushes. The practice of shifting the brush position for each current variation is not
                  practiced except in small generators. In larger generators, other means are taken to
                  eliminate armature reaction. Compensating windings or interpoles are used for this
                  purpose (see Fig. 2.6.4).



                  PARALLEL OPERATION
                  The general rule is for the use of machines with flat-compounded characteristics
                  when running in parallel. When two DC machines are operating in parallel, a change
                  in load will cause change in speed and therefore in terminal voltage. Therefore,
                  ‘equaliser’ connections will be required to avoid the machine with higher revolutions
   93   94   95   96   97   98   99   100   101   102   103