Page 221 - Offshore Electrical Engineering Manual
P. 221

208    CHAPTER 1  Alternator Faults and Protection Devices




                         OVERLOAD PROTECTION
                         The larger offshore alternators will not have overload protection as such, but
                         resistance temperature devices (RTDs) are buried in the stator windings and will
                         give alarm and trip signals at temperatures where overloading or other abnor-
                         mal conditions such as excitation faults have occurred. The temperature protec-
                         tion will avoid unnecessary shortening of insulation life. With small emergency
                         generators, the associated circuit breaker should be provided with a thermal
                         element.

                         OVERCURRENT PROTECTION

                         To protect the generator from downstream faults, overcurrent relays of either the
                         inverse definite minimum time (IDMT) or definite time type are required. The
                         protection relay must provide sufficient time for downstream protection relays
                         to operate to clear the fault, but this time must be within the time rating of the
                         alternator. Larger generators are usually provided with permanent magnet pilot
                         exciters to maintain a fault current of around three times rated current contin-
                         uously after the transient short-circuit current has decayed away. This can be
                         maintained usually for an absolute maximum of 10 s before the generator over-
                         heats. However, it should not be necessary to approach even 5 s in order to oper-
                         ate downstream protection, and the damage due to arcing faults if such a large
                         amount of fault energy is let through can be extensive. It is therefore advisable
                         to keep fault times to a minimum by good relay coordination. With small self-
                         excited generators, it is important to specify a ‘fault current maintenance kit’
                         consisting of a voltage sensitive relay and compounding current transformers
                         (CTs) designed to maintain excitation current when the output voltage collapses
                         because of a fault. If reasonable coordination cannot be obtained using normal
                         IDMT or definite time relays, voltage controlled or voltage restraint type relay
                         can be used to take advantage of close-up fault voltage collapse. An example of
                         this is given at the end of this chapter.

                         PHASE AND INTERTURN FAULTS
                         Stator and interturn faults are relatively uncommon but are more likely to occur at
                         the ends of the windings or in the terminal box. Insulation failures between phases
                         may be sensed by differential protection. Both types of fault will cause heating and
                         possibly a fire, which should be detected by suitable smoke detection in the acoustic
                         hood, if not by the RTDs or the differential protection.


                         WINDING PROTECTION
                         Restricted earth fault (if the individual phases are not accessible at the neutral end)
                         or phase and earth fault circulating current type protection is usually provided on
   216   217   218   219   220   221   222   223   224   225   226