Page 225 - Offshore Electrical Engineering Manual
P. 225

212    CHAPTER 2  Transformer Faults and Protection Devices




                         like. Offshore transformers are as likely to suffer from abnormal system operation as
                         their onshore counterparts. The maintenance of system voltage and frequency may be
                         dependent for long periods on the satisfactory operation of one generator package. The
                         governor or automatic voltage regulator of this package may be set low or high, or may
                         be subject to drift within the limits of the voltage and frequency protection. Therefore,
                         transformers may be subject to variations in voltage and frequency. High voltage and
                         low frequency may together cause shifting of flux in structural parts of the transformer,
                         which will heat up and destroy insulation. The transformer must also be protected from
                         overloads and overcurrents due to downstream faults.



                         MAGNETISING INRUSH
                         Magnetising inrush is a normal healthy but transient condition associated with the
                         establishment of linking flux between the windings. However, if it is forgotten when
                         setting upstream overcurrent protection relays, it may cause nuisance tripping. Values
                         quoted by transformer manufacturers are in the region of 12 times full load for 15 ms.



                         OVERCURRENT PROTECTION
                         A common arrangement offshore is to protect the primary winding of the transform-
                         ers between the main (medium voltage) and the production (LV) switchboards with
                         inverse definite minimum time overcurrent relays graded with the main generator
                         overcurrent protection. The relay may have an earth fault element that detects earth
                         faults in the primary winding only.



                         RESTRICTED EARTH FAULT PROTECTION

                         With the restricted earth fault scheme, the residual current obtained from a current
                         transformer (CT) in each line is balanced against the current from a CT in the neutral.
                         The neutral is usually solidly earthed and therefore a healthy fault current will be
                         produced even from a fault at the last turn of the winding (i.e., closest to the neutral).
                         As faults are only detected between the line CTs and the neutral CT, only the star
                         secondary is protected, using a sensitive instantaneous relay.




                         DIFFERENTIAL PROTECTION
                         Differential protection is rarely used on transformers offshore. However, it does have
                         the advantage over restricted earth fault protection in that both primary and secondary
                         windings are protected from both earth and phase-to-phase faults. The relay will only
                         operate for faults appearing in the protection zone between the sets of sensing CTs at
   220   221   222   223   224   225   226   227   228   229   230