Page 222 - Offshore Electrical Engineering Manual
P. 222

Introduction  209




                  machines of rating 500 kW and larger, although this threshold will vary with the
                  degree of criticality of the supply. A stabilising resistor must be provided in series
                  with the relay to prevent CT saturation effects causing the relay to operate in faulty
                  conditions. The method of calculating the resistance value is given in an example at
                  the end of the chapter.

                  OVER-/UNDERVOLTAGE PROTECTION

                  This facility is often provided as part of the generator’s automatic voltage regulator
                  (AVR), but if this is not the case, it must be included in the generator control panel
                  or switchboard. If fed from a separate voltage transformer (VT), it may duplicate
                  the AVR facility, so that failure of one set of VT fuses cannot lead to loss of voltage
                  control and/or monitoring.

                  OVER-/UNDERFREQUENCY PROTECTION
                  This facility is often provided by the prime mover governor, but as it is more criti-
                  cal on a generator isolated from a grid system, it is often duplicated electrically.
                  This ensures that the circuit breaker trips before damage is done to motors or driven
                  machinery, even if the prime mover overruns because of gas ingestion at the air
                  intake (see PART 2 Chapter 4).


                  UNBALANCED LOADING AND NEGATIVE PHASE
                  SEQUENCE PROTECTION
                  If the platform load is unbalanced, there will be a negative phase sequence com-
                  ponent in the generator load current which, if excessive and over a long period,
                  will cause overheating of the rotor. On the larger offshore generator packages, it is
                  therefore necessary to fit negative phase sequence protection, which after a timed
                  period corresponding to the thermal characteristic of the rotor, will trip the genera-
                  tor. As the source of negative sequence current is external to the generators and will
                  lead to the tripping of all the generators if not removed, it is normal to provide an
                  alarm at onset of the problem so that operators may have time to find the offending
                  load before production shutdown occurs. A suitable setting value should be sought
                  from the generator manufacturers in each case, but a value no greater than 30% is
                  recommended.


                  ROTOR FAULTS
                  The exciter output current on brushless machines is monitored and should a rotating
                  diode go short circuit, an alarm will be annunciated on the generator control panel.
                  This facility is usually included in the AVR circuitry, and therefore, it is not likely to
                  be included in the discrete protection relay suite.
   217   218   219   220   221   222   223   224   225   226   227