Page 224 - Offshore Electrical Engineering Manual
P. 224

CHAPTER


                  Transformer Faults and                                     2

                  Protection Devices






                  TRANSFORMER FAULTS

                  EARTH FAULTS
                  The magnitude of any fault current flowing in a transformer will be a function of the
                  winding arrangement (and hence leakage reactance) and the type of earthing (solid
                  or impedance). Most offshore distribution transformers, however, are of the delta star
                  (usually Dy11) type, the only exceptions normally being those used for supplying the
                  drilling silicon controlled rectifiers. With the usual solidly earthed star point arrange-
                  ment, the fault current will be highest when the fault is near neutral. There is no zero-
                  sequence path through such a transformer and therefore coordination is not required
                  with any earth fault protection on the primary side. The magnitude of any earth fault
                  on the delta primary winding will be governed by the type of earthing in that part of
                  the system. If it is fed from the main switchboard, it will probably be limited by the
                  generator earthing resistors.

                  PHASE-TO-PHASE FAULTS

                  Faults between phases on offshore transformers are relatively rare, especially with
                  the newer sealed or encapsulated types of transformer. Such a fault is likely to pro-
                  duce a substantial current large enough to be detected quickly by upstream overcur-
                  rent protection.


                  CORE AND INTERTURN FAULTS
                  Although interturn faults are unlikely on offshore distribution transformers because of
                  the relatively low voltages (LVs), the fire hazard is such that their probability cannot be
                  ignored. A fault in a few turns will cause a high current to flow in the short-circuited
                  loop and produce a dangerous local hot spot. A conducting path through core lamina-
                  tions will also cause severe local heating. It is difficult to detect such a fault in a resin-
                  encapsulated transformer. Offshore distribution transformers are less likely to suffer
                  line surges or steep fronted impulse voltages, as cabling is relatively short and lightning
                  strikes are rare. However, moisture ingress is more likely in the offshore environment,
                  and mechanical vibration levels are higher, making chafing and cracking of insulation
                  more likely, so the possibility of interturn faults cannot be ignored. If the transformer
                  is housed in a tank containing insulating oil, there is always a danger that the tank will
                  corrode in the salt-laden atmosphere, or will be damaged by crane operations or the

                  Offshore Electrical Engineering Manual. https://doi.org/10.1016/B978-0-12-385499-5.00022-4  211
                  Copyright © 2018 Elsevier Inc. All rights reserved.
   219   220   221   222   223   224   225   226   227   228   229