Page 235 - Offshore Electrical Engineering Manual
P. 235

222    CHAPTER 4  Busbar Protection















                         FIGURE 4.4.1
                         Simple plain overcurrent busbar protection scheme.



















                         FIGURE 4.4.2
                         Simple directional overcurrent busbar protection scheme.


                         arrangement will preserve the two healthy sections, provided the fault is not
                         on the central section. As central section faults rely on upstream protection for
                         clearance, this section should be kept as short and uncomplicated as possible
                         for good reliability. This arrangement could be used for the connection of a
                         third generator, with all outgoing feeders (except third generator auxiliaries)
                         fed from the end sections (see Fig. 4.4.2).



                         UNRESTRICTED EARTH FAULT PROTECTION
                         On main generator switchboards, either inverse definite minimum time or definite
                         time earth fault characteristics may be used, but the use of definite time is often pref-
                         erable, as fault current magnitudes are restricted by the generator neutral earthing
                         resistors. Any relay used should be designed so as not to be sensitive to third har-
                         monic currents, if the generator winding configuration is such that significant third
                         harmonic currents may circulate. Low-voltage switchboards are more likely to suffer
   230   231   232   233   234   235   236   237   238   239   240