Page 236 - Offshore Electrical Engineering Manual
P. 236

Frame Earth Protection  223




                  arcing faults than medium-voltage switchboards because with increasing voltage, the
                  reduction in fault current due to arc resistance becomes less pronounced as the arc
                  voltage ceases to be a significant proportion of the total fault circuit driving voltage
                  (see Reference 1). Hence, the importance of earth fault protection for low-voltage
                  switchboards is stressed.



                  FRAME EARTH PROTECTION
                  This type of system has been used successfully offshore and consists of a frame earth
                  relay and neutral check relay arranged to monitor earth fault current flows into and out
                  of the switchboard. A simple frame earth system is illustrated in Fig. 4.4.3. Care must
                  be taken when installing the switchboard into the module such that it is and will remain
                  insulated from the steel of the module construction. The generator earthing resistor and
                  the switchboard frame should be earthed at the same point to avoid both series earth
                  connections and increasing the risk of the fault current being limited below the oper-
                  ating setting of the relay by a poor connection due to corrosion of the decking steel.
                  This is less likely to be a problem in an onshore substation using earth electrodes.
































                  FIGURE 4.4.3
                  Busbar frame earth protection scheme.
                                           Courtesy GEC Alsthom Measurements, now part of GE Grid Solutions.
   231   232   233   234   235   236   237   238   239   240   241