228    CHAPTER 5  Conductor Sizing, Load Flow and Fault Calculation


















































                         FIGURE 4.5.1
                         Miniature circuit breaker and fuse characteristic comparison. LV, low voltage; MCCB,
                         moulded case circuit breaker.
                                                  Courtesy GEC Alstom Measurements, now GE Alstom Grid Solutions.


                         proportion of the platform load is on the switchboard being fed. This is because
                         the steady-state fault current available from the platform generators will be of
                         the order of three to four times the full-load current; therefore, if fault clearance
                         times are to be kept short, generator and feeder relay current settings will need to
                         be close. Voltage-controlled relays may be used on generator circuit breakers to
                         overcome this problem, as discussed earlier for generator protection (see PART 4
                         Chapter 1).