Page 245 - Offshore Electrical Engineering Manual
P. 245

232    CHAPTER 5  Conductor Sizing, Load Flow and Fault Calculation













































                         FIGURE 4.5.2
                         Schematic of small-generator fault current maintenance circuit. AVR, automatic voltage
                         regulator.


                         maintenance unit as shown in Fig. 4.5.2. This device is basically a compounding
                         circuit which feeds a current proportional to output current back to the exciter
                         field. When the output current reaches a threshold value well above the normal
                         load current, a relay operates, switching in the compounding circuit. Thus a high
                         output current is maintained by this feedback arrangement until the operation of
                         definite time overcurrent protection, which is set to prevent the generator thermal
                         rating being exceeded.


                         MAIN GENERATOR FAULT CURRENTS
                         In this example, one generator is rated at 15.0 MW. The alternator has the follow-
                         ing parameters: rating 17.7 MVA at a power factor of 0.85 and voltage of 6.6 kV;
   240   241   242   243   244   245   246   247   248   249   250