Page 250 - Offshore Electrical Engineering Manual
P. 250

CHAPTER


                  Calculation of Load                                        6

                  Flow, Prospective Fault

                  Currents and Transient

                  Disturbances





                  FAULT CALCULATION
                  The following calculations and information are not exhaustive but are intended to
                  give the reader sufficient knowledge to enable switchgear of adequate load and fault
                  current rating to be specified. The subject may be studied in more detail by reading
                  the relevant documents listed in Appendix 1. The nomenclature used is generally as
                  given in ‘Power System Protection’ (IET).
                     When a short circuit occurs in a distribution switchboard, the resulting fault cur-
                  rent can be large enough to damage both the switchboard and associated cables due
                  to thermal and electromagnetic effects. The thermal effects will be proportional to
                  the duration of the fault current to a large extent and this time will depend on the
                  characteristics of the nearest upstream automatic protective device which should
                  operate to clear the fault.
                    Arcing faults due to water or dirt ingress are most unlikely in the switchboards of
                  land-based installations, but from experience, they need to be catered for offshore.
                  For switchboards operating with generators of 10 MW or more, it is usually not dif-
                  ficult to avoid the problem of long clearance times for resistive faults. However, with
                  the smaller generators clearance times of several seconds may be required because of
                  the relatively low prospective fault currents available. (See PART 4 Chapter 4) With
                  small emergency generators, pilot exciters are not normally provided and the supply
                  for the main exciter is derived from the generator output. This arrangement is not rec-
                  ommended, as it allows the collapse of generator output current within milliseconds
                  of the onset of a fault. With such small generators even sub-transient fault currents
                  are small, and it is unlikely that downstream protection relays set to operate for ‘nor-
                  mal’ generation will have operated before the output collapse. It is usual to provide a
                  fault current maintenance unit as shown in Fig. 4.6.2. This device is basically a ‘com-
                  pounding’ circuit which feeds a current proportional to output current back to the
                  exciter field. When the output current reaches a threshold value well above normal
                  load current, a relay operates, switching in the compounding circuit. Thus a high out-
                  put current is maintained by this feedback arrangement until definite time overcurrent
                  protection, set to prevent the generator thermal rating being exceeded, operates.
                    A worked example for use in setting Main Generator Protection is given in
                  PART 4 Chapter 5.

                  Offshore Electrical Engineering Manual. https://doi.org/10.1016/B978-0-12-385499-5.00026-1  237
                  Copyright © 2018 Elsevier Inc. All rights reserved.
   245   246   247   248   249   250   251   252   253   254   255