Worked Example: Fault Calculation  235




                  connected to the LV switchboard by a 2 MVA transformer with 440 V secondary
                  winding. Then the sequence reactances (pu) are as follows:



                                   X 1              X 2              X 0
                   At transformer rating  0.13      0.11             0.11
                   On the base MVA  1.1505          0.974            0.974

                     Summing generator and transformer reactances,
                                     X 1 = 0.0912 + 1.1505 = 1.2417 pu
                                     X 2 = 0.104 + 0.974 = 1.078 pu
                                     X 0 = 0.974 = 0.974 pu
                     Hence,
                              (X 1 + X 2 ) = 1.2417 + 1.078 = 2.3197 pu
                              (X 1 + X 2 + X 0 ) = 1.2417 + 1.078 + 0.974 = 3.294 pu
                     Therefore the LV system fault currents are
                                                         17.7
                             Three ‐ phase fault current =        = 18.7 kA
                                                    3 × 0.44 × 1.2417
                                                          17.7
                            Phase ‐ to ‐ phase fault current =    = 17.34 kA
                                                      0.44 × 2.3197
                                                    3 × 17.7
                                 Earth fault current =      = 21.15 kA
                                                  0.44 × 3.294
                     The workings required for protection settings of the same scenario are continued
                  in PART 4 Chapter 7.