Page 240 - Offshore Electrical Engineering Manual
P. 240

CHAPTER


                  Feeder Protection,                                         5

                  Conductor Sizing, Load

                  Flow and Fault Calculation





                  FUSES
                  Low-voltage (LV) distribution systems in offshore installations are protected by
                  fuses in the same way as their onshore counterparts. Although the Institution of
                  Electrical Engineers (IEE) Wiring Regulations specifically excludes offshore instal-
                  lations from its scope (Part 1 paragraph II-3(vii)), the document that it refers to (IEE
                  Recommendations for the Electrical and Electronic Equipment of Mobile and Fixed
                  Offshore Installations) has been replaced by BS IEC 61892, Mobile and fixed off-
                  shore units. Electrical installations. The methods of calculation given in the IEE
                  Wiring Regulations are normally adopted when designing lighting and small power
                  distribution systems, particularly for accommodation modules.
                     The use and limitations of high rupturing capacity fuses are discussed in PART 2
                  Chapter 5.



                  MINIATURE CIRCUIT BREAKERS

                  In most situations, miniature circuit breakers (MCBs) may be used as an alternative
                  to fuses where the fault rating of the MCB is sufficiently high. However, because
                  of the different shape of the MCB tripping characteristic compared with that of a
                  fuse (see Fig. 4.5.1), it is not advisable to mix fuses with MCBs in the same circuit
                  if discrimination is required. The degree of discrimination between one MCB and
                  another, and between MCBs and fuses, varies with the BS EN 60898-1 MCB type,
                  but generally a better discrimination can be obtained using fuses.
                     MCBs with fault current ratings more than 16 kA are now available and are in
                  common use offshore, where they save weight and reduce the quantity and type of
                  spare fuses stocked. MCBs used offshore must provide positive indication of contact
                  clearance and must be padlockable when in the open position.



                  OVERCURRENT AND EARTH FAULT PROTECTION
                  Most of the conventional forms of short cable feeder protection may be used off-
                  shore. The use of inverse definite minimum time (IDMT) overcurrent and residu-
                  ally connected earth fault relays may give discrimination problems if a large

                  Offshore Electrical Engineering Manual. https://doi.org/10.1016/B978-0-12-385499-5.00025-X  227
                  Copyright © 2018 Elsevier Inc. All rights reserved.
   235   236   237   238   239   240   241   242   243   244   245