Page 237 - Offshore Electrical Engineering Manual
P. 237

224    CHAPTER 4  Busbar Protection




                         However, earth connections should be maintained and checked for resistance value
                         on a routine basis, particularly to prevent dangerous potentials appearing on the
                         switchboard frame during fault conditions. An earth or bonding bar interconnects the
                         framework of each cubicle, but is only earthed via the conductor monitored by the
                         frame earth relay. Where the circuit breakers are in trucks, the truck must also have
                         a heavy current earth connection to the bonding bar to allow earth fault current flow
                         from the circuit breaker. To prevent currents induced in cables from causing spurious
                         tripping, the gland plates at the switchboard end should be insulated from the switch-
                         board frame but earthed to a second separate earth bar which is directly earthed to
                         the main earth point.




                         DIFFERENTIAL PROTECTION
                         Kirchhoff’s first law may be directly applied by monitoring incoming and outgo-
                         ing currents at all the switchboard external circuit connections, summating them
                         and detecting the error, if an internal switchboard fault exists. The switchboard
                         may be divided into a series of zones, and each zone boundary should be treated
                         in the same way, as shown in Fig. 4.4.4. The relay settings must be such that the
                         transient flux produced by through-fault currents will not cause tripping because
                         of the imbalance due to unequal burden or saturation of CTs. By the use of high-
                         impedance relays with series stabilising resistors, the voltage across the relay dur-
                         ing through-faults, known as the stability voltage, may be kept below the relay
                         operating voltage. The minimum value of the stabilising resistor for stability may
                         be calculated as follows:



                                          V S = Relay setting current × (R SR + R R )

                         where V , stability voltage; R , resistance of stabilising resistor and R , resistance
                                                                                  R
                                                 SR
                                S
                         of the relay coil.
                            An example calculation is given in PART 4 Chapter 7.
                            For fault calculations see PART 4 Chapter 6.
                            For relay discrimination topics see PART 4 Chapter 7.
   232   233   234   235   236   237   238   239   240   241   242