Page 275 - Offshore Electrical Engineering Manual
P. 275

262    CHAPTER 7  Protection and Discrimination




                         WORKED EXAMPLE: SETTING VOLTAGE CONTROLLED
                         OVERCURRENT RELAYS

                         Some overcurrent relays provide dual inverse characteristics. The less sensitive
                         characteristic gives a longer time interval for clearance of downstream faults, and
                         the more sensitive characteristic removes close-up faults more quickly. Faults
                         close to the generator have less impedance and hence produce greater voltage
                         dips. At a set level of voltage dip, the relay will switch from one characteristic
                         to the other.
                            In this case we will set the voltage to discriminate between a fault upstream
                         (giving rise to a large voltage dip) and a fault downstream of a transformer (pro-
                         ducing a smaller voltage dip). The inset on Fig. 4.7.6 shows the equivalent dia-
                         gram. The maximum voltage dip occurs when the transformer reactance X  is a
                                                                                        x








































                         FIGURE 4.7.6
                         Graph of voltage downstream of transformers during system fault: Example for voltage
                         controlled relays.
   270   271   272   273   274   275   276   277   278   279   280