Page 273 - Offshore Electrical Engineering Manual
P. 273

260    CHAPTER 7  Protection and Discrimination




                            Fuse B1 operates at t = 0.01 s at 2400 A, from the fuse characteristic, with fault
                         current obtained from computer results.
                            From the GEC Guide, the relay Z operating time is:
                                                t + 0.45 t + 0.15 = 0.164 s
                            The PSM is 2400/450 = 5.33. Therefore the relay operating time at a PSM of
                         5.33 and a TMS of 1 is 1.8 s, from the relay characteristic. The required TMS is
                         0.164/1.8 = 0.09 ≈ 0.1.
                            In this case, a check was made against the relay characteristic. It was found that
                         the curve for TMS = 0.1 gives an operating time of only 0.14 s at a PSM of 5.33. As
                         this is too fast, the time setting was adjusted to 0.2. Relays U, T and Y may be set in
                         a similar manner.


                         RELAY F: RANGE 10%–200%, CT RATIO 1500/1; 10 VA 5P10
                         This relay must coordinate with earth fault relays Z and U and with the largest outgo-
                         ing fuse in the accommodation switchboard, fuse U, 400 A.
                            (This assumes that coordination with fuse U assures coordination with relay.)
                            Set relay F at three times fuse U rating, i.e., 3 × 400 A = 1200 A. Then the nearest
                         current setting is:
                                                  0.8 × 1500 = 1200 A
                            From the SC studies, the maximum earth fault current is 55.458 kA. At this cur-
                         rent, fuses Z and U operate in 0.01 s, from the fuse characteristics. From the GEC
                         Guide, the relay F operating time is:
                                                  t + 0.4 + 0.15 = 0.164s
                            From the SC studies, the average earth fault current at 0.164 s is 51.44 kA.
                            As a PSM, this is 51,440/1200 = 42.9.
                            From the relay characteristics, the relay operating time at a PSM of 42.9 and a
                         TMS of 1 is 0.25 s. Therefore the required TMS is 0.164/0.25 = 0.66 ≪ 0.7.
                            It is necessary to carry out a relay saturation check. The relay impedance at the
                                                         2
                         0.8 setting is given by (relay VA)/(0.8)  = 0.39 Ω. Allowing 1 Ω for lead resistance
                         gives 1.39 Ω.
                            Thus the secondary burden is 1.39 × (1 A) = 1.39 VA. Therefore:

                                 I maxunsat = 10 VA × (10/1.39) × (1500/1)
                                       = 107.9 kA (which is above the maximum fault current).

                            Note that if a saturation current significantly lower than the fault current is
                         obtained, it is advisable to select a different CT. The burdens associated with elec-
                         tronic relays are much lower than those used above for induction disc types, and
                         because of this are less likely to give rise to saturation problems.
   268   269   270   271   272   273   274   275   276   277   278