Overcurrent Relay Setting  255









































                  FIGURE 4.7.2
                  Overcurrent discrimination flowchart.


                  OVERCURRENT RELAY SETTING

                  RELAY F: RANGE 10%–200%, CT RATIO 1500/1
                  From the load flow study:
                                  Standing load = 50 kW + j20 kVA r ≈ 71 A
                                  Motor load (2 motors) = 96 kW + j40 kVA r
                           Motor load (1 motor) = 96/2 + j40/2 = 52 kVA = 68 A

                                   Motor starting current ≈ 6 × 68 A = 408 A
                     Therefore the maximum load including motor starting, assuming that the currents
                  are in phase, is
                                          71 + 68 + 408 = 547 A