Page 267 - Offshore Electrical Engineering Manual
P. 267

254    CHAPTER 7  Protection and Discrimination




                          Table 4.7.1  Synchronous Machine Parameters
                                         Per Unit Value to Machine
                                                  Base            Per Unit Value to 10 MVA Base
                                       Production    Emergency    Production    Emergency
                          Description  Generator     Generator    Generator     Generator
                          Rated MVA    4.729         1.313
                          Rated voltage   6.6        0.44
                          (kV)
                                       0.181         0.233        0.383         1.775
                          Subtransient  ′
                                  X
                          reactance  d
                          Transient reac-  0.252     0.46         0.533         3.503
                                ′
                              X
                          tance  d
                          Synchronous   1.95         2.45         4.123         18.66
                          reactance
                          Potier       0.166         0.22         0.351         1.676
                          reactance
                          Saturation   1.45          1.562        1.45          1.562
                          factor
                          Negative-    0.255         0.27         0.539         2.056
                          sequence
                          reactance
                          Zero-sequence   0.103      0.14         0.218         1.066
                          reactance



                         OPERATING CONDITIONS

                         Mode 1: Maximum generation: four production generators, maximum standing load
                         and all motors running. Main switchboard bus section closed; other switchboard bus
                         sections open.
                            Mode 2: Minimum generation: one production generator running with no motors
                         operating.
                            Mode 3: Emergency generation only.
                            The low-voltage switchboards are provided with two feeders. The normal con-
                         figuration is with low-voltage switchboard bus section switches open, with each side
                         fed by a separate feeder.
                            From Fig. 4.7.1 an overcurrent discrimination flow chart can be constructed, as
                         in Fig. 4.7.2. All the devices including fuses should be identified, and the flow is
                         downstream from left to right. The coordination exercise can now begin with the
                         relays furthest downstream. It should not be necessary to start with the fuses U and
                         Z as these obviously have fixed characteristics. However, it may still be necessary to
                         change the fuses for ones with more suitable characteristics if grading problems are
                         experienced.
   262   263   264   265   266   267   268   269   270   271   272